Description
CONSTRUCTION
Conductor: Plain annealed copper, Class 2, Stranded circular or compacted
Fire barrier: Mica tape (MGT)
Insulation:Cross-Linked Polyethylene (XLPE) compound
Insulation colour:
2 cores: Brown, Blue
3 cores: Brown, Black, Grey or Brown, Blue, Green/Yellow
4 cores: Brown, Black, Grey, Blue
5 cores: Brown, Black, Grey, Blue, Green/Yellow or White with Black numberings
6 cores and above: White with Black numberings
Assembly: Cores cabled together and bound with binder tape
Outer sheath: Low-Smoke Zero-Halogen (LSZH) compound with anti-termite characteristics and UV resistant
Outer sheath colour: Orange or others
ELECTRICAL CHARACTERISTICS
Operating voltage U0 / U: 300/500V
Operating temperature: -15°C to +90°C
Final short circuit temperature: 250°C
Test voltage: 2kV for 1 minute
REFERENCE STANDARDS
Design specification: BS EN50288-7
Conductor: IEC60228, BS EN60228
Fire resistance: BS6387 (C,W,Z), SS299 (C,W,Z), IEC60331
Flame retardancy: IEC60332-3-22, BS EN60332-3-22
Low-Smoke Zero-Halogen: IEC61034-2, BS EN61034-2, IEC60754-1, IEC60754-2, BS EN60754-1, BS EN60754-2
INSTALLATION REFERENCE
Minimum bending radius (mm): 8 x cable overall diameter
Maximum pulling tension: 50N/mm²
Related products
Air Circuit Breakers
Air Circuit Breakers
Schneider Electric Control & Signalling Tower Lights XVBC2G5
Schneider Electric Control & Signalling Tower Lights DL2EDM4SB
Schneider Electric Moulded Case Circuit Breakers 33225
Schneider Electric Moulded Case Circuit Breakers 33251
Samick TBR16UU Aluminum Case Unit
Schneider Electric Earth Leakage Circuit Protector A9D60616
Schneider Electric Moulded Case Circuit Breakers EZASHT048DC 