Description
CONSTRUCTION
Conductor: Plain annealed copper, Class 2 Stranded circular or compacted
Fire barrier: Mica tape (MGT)
Insulation: Cross-link Polyethylene (XLPE) compound
Insulation colour: Natural
Outer sheath: Low-Smoke Zero-Halogen (LSZH) compound with anti-termite characteristics and UV resistant
Outer sheath colour: Orange or others
ELECTRICAL CHARACTERISTICS
Operating voltage, U0/U: 600/1000V
Operating temperature: -15°C to +90°C
Final short circuit temperature: 250°C
Test Voltage: 3.5kV for 5 minutes
REFERENCE STANDARDS
Design specification: IEC60502-1
Conductor: IEC60228, BS EN60228
Fire resistance: BS6387 (C,W,Z), SS299 (C), IEC60331
Flame retardancy: IEC60332-3-22, BS EN60332-3-22
Low-Smoke Zero-Halogen: IEC61034-2, BS EN61034-2, IEC60754-1, IEC60754-2, BS EN60754-1, BS EN60754-2
INSTALLATION REFERENCE
Minimum bending radius (mm): 8 x cable overall diameter
Maximum pulling tension: 50N/mm²